48v inverter output short circuit and output voltage protection instructions

Column:Industry News Time:2021-10-19
When the inverter output feedback does not have a zero-crossing point for 64ms continuously,

(1) Output short-circuit protection of the inverter

When the inverter output feedback does not have a zero-crossing point for 64ms continuously, it is regarded as an output short circuit, the UPS output is turned off, the UPS beeps for a long time and an alarm is displayed on the panel.

(2) Output voltage protection of the inverter

When the inverter output feedback voltage is lower than 140V or higher than 276V for 80ms continuously, it is regarded as output undervoltage or overvoltage for protection, the UPS transfers to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(3) BUS overvoltage protection of the inverter

When the BUS voltage exceeds 440V for 64ms continuously, it is considered that the BUS is over-voltage and protected, the UPS transfers to the bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(4) Inverter current limiting protection

The protection circuit monitors the output current value. If it exceeds 3.6 times the rated current, the current-limiting protection circuit immediately turns off the PWM and resets the PWM at a 19.2kHz cycle until the output current value is less than 3.6 times the rated current.

(5) Over-temperature protection of the inverter

When the system temperature is too high, the temperature switch trips, making the UPS transfer to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel (detection time 0.5s).

(6) Load protection of inverter


110%~130%

If the UPS detects that the load exceeds 110% before jumping from the bypass to the inverter, it cannot enter the inverter state. At this time, the UPS beeps once every 0.5s and displays the status on the panel. If the load is detected between 110% and 130% after power-on, the UPS will beep once every 0.5s and display the status on the panel. After 10s, the UPS will switch to bypass mode; after that, if the load is reduced to below 100%, the UPS Restart the soft boot. If the UPS detects that the load is between 110% and 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; if the load is not reduced below 100%, the UPS will transfer to bypass after 10s Mode, this state can only be released by pressing the OFF button.


Greater than 130%

If the load is detected to be greater than 130% after power-on, the UPS will beep once every 0.5s, and the status will be displayed on the panel, and the UPS will transfer to the bypass state. After that, if the load is reduced to below 100%, the UPS restarts. If the UPS detects that the load is greater than 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; at the same time, the UPS will switch to bypass mode; this status can only be released by pressing the OFF button.


久久99动漫精品国产成人久| 国产亚洲精品精华液好用吗| 国产精品美女久久久| 精品国产一区二区三区无码| 国产AV熟女一区二区三区| A级毛片在线观看| 暴力调教一区二区三区| 国产美女视频黄A片免费观看软件| 欧美日韩国产三级在线| 不许人间见白头| 国内揄拍国内精品少妇国语| 性xxxxfreexxxxxvideo| 人妻无码一区二区三区| 性欧美XXXX| 亚洲午夜无码久久久久| 亚洲精品乱码久久久久久| 娇小萝被两个黑人用半米长| 日本爽快片18禁片免费久久| 国产亚洲午夜精品a一区二区三区| 亚洲色欲色欲www| 亚洲精品国产精品乱码不99| WWW国产精品内射老熟女| 亚洲av一二三区白石茉莉奈| 亚洲啪AV永久无码精品放毛片| 国产撸撸热视频| 人妻无码久久一区二区三区免费| 久久久久亚洲AV无码专区首| 国产精品久久久三级精品久久久三级| 97碰碰碰人妻无码视频| 差差漫画在线看漫画免费弹窗下载 | 国产熟妇无码A片AAA毛片视频| 亚洲欧美日韩综合一区在线观看| 国产精品三级在线观看无码| 亚洲综合一区二区精品专区| 久久精品视频在线看88| 久久69国产精品久久蜜臀| 女人18毛片水真多| 欧美AV在线观看| 精品白嫩BBWBBWBBW| 无码人妻丰满熟妇啪啪网站| 尤物色视频网站在线观看|